GWIEC PRODUCT SELECTION GUIDE · PRINTED PAGES 01–10
Miniature Circuit Breakers
Select by AC or DC application, pole configuration, rated current, breaking capacity and trip curve.
Compare Earth Leakage Circuit Breakers →
G-L7 High Breaking Capacity Miniature Circuit Breakers
L7-GL-FUSE CATALOG · PRINTED PAGES 01–05
The G-L7 MCB provides overload and short-circuit protection. The catalog includes standard and plug-in G-L7-63 products, separate C and D curve order matrices, and load and energy curves.
G-L7-63 standard variants
G-L7-63 plug-in variants
Electrical specifications · p. 02 | Parameter | Catalog value |
| Rated operational voltage Ue | 230/400 V AC, 50/60 Hz |
| Rated short-circuit breaking capacity Icn | 10 kA for 0.5–63 A as listed on page 02 |
| DC capability noted on page 02 | Standard G-L7 single pole: up to 48 V DC, 10 kA; G-L7-DC single pole: up to 250 V DC, 6 kA |
| Trip characteristics | C and D; page 03 lists instantaneous bands of 5–10 × In (C) and 10–20 × In (D) |
| Backup fuse shown | 100 A gL for the condition marked >10 kA |
| Energy limitation class shown | 3 |
| Ambient temperature | −5 to +40 °C |
| Enclosure after installation | IP40 |
| Electrical endurance | At least 8,000 switching operations |
| Mechanical endurance | At least 20,000 switching operations |
Mechanical data · p. 02 | Parameter | Catalog value |
| Exposed face height | 45 mm |
| Enclosure height | 80 mm |
| Module width | 17.5 mm per pole |
| Mounting | 35 mm DIN rail |
| Terminals | Dual-purpose terminals for busbar and wire |
| Connection range | 1–25 mm² conductor; busbar thickness 0.8–2 mm |
Accessories listed · p. 02 | Parameter | Catalog value |
| Auxiliary contact | G-Z7-AHK |
| Alarm contact | G-Z7-NHK |
| Shunt release | G-Z7-ASA |
| Undervoltage release | G-Z7-USA |
Catalog verification. The page 03 2P D-curve column repeats the 1P order codes. Page 04 also prints G-L7-6/1N-2/C in the 3P+N column. Both are reproduced as printed and require confirmation before ordering.
Catalog page 01 · G-L7-63 product overview
G-L7-63 product range | Product | Voltage | Catalog rated currents |
| G-L7-63 | 230/400 V | 6, 10, 16, 20, 25, 32, 40, 50, 63 A |
Open original at full size ↗ Catalog page 01 · G-L7-63 plug-in product overview
G-L7-63 plug-in range | Product | Voltage | Catalog rated currents |
| G-L7-63 plug-in | 230/400 V | 6, 10, 16, 20, 25, 32, 40, 50, 63 A |
Open original at full size ↗ Catalog page 03 · 1P, 1P+N and 2P ordering matrix with circuit diagrams
C curve | In (A) | 1P | 1P+N | 2P |
| 0.5 | G-L7-0.5/1/C | — | G-L7-0.5/2/C |
| 1 | G-L7-1/1/C | — | G-L7-1/2/C |
| 2 | G-L7-2/1/C | — | G-L7-2/2/C |
| 3 | G-L7-3/1/C | — | G-L7-3/2/C |
| 4 | G-L7-4/1/C | — | G-L7-4/2/C |
| 6 | G-L7-6/1/C | G-L7-6/1N-2/C | G-L7-6/2/C |
| 10 | G-L7-10/1/C | G-L7-10/1N-2/C | G-L7-10/2/C |
| 16 | G-L7-16/1/C | G-L7-16/1N-2/C | G-L7-16/2/C |
| 20 | G-L7-20/1/C | G-L7-20/1N-2/C | G-L7-20/2/C |
| 25 | G-L7-25/1/C | G-L7-25/1N-2/C | G-L7-25/2/C |
| 32 | G-L7-32/1/C | G-L7-32/1N-2/C | G-L7-32/2/C |
| 40 | G-L7-40/1/C | G-L7-40/1N-2/C | G-L7-40/2/C |
| 50 | G-L7-50/1/C | G-L7-50/1N-2/C | G-L7-50/2/C |
| 63 | G-L7-63/1/C | G-L7-63/1N-2/C | G-L7-63/2/C |
D curve | In (A) | 1P | 1P+N | 2P (as printed) |
| 2 | G-L7-2/1/D | — | G-L7-2/1/D |
| 4 | G-L7-4/1/D | — | G-L7-4/1/D |
| 6 | G-L7-6/1/D | — | G-L7-6/1/D |
| 10 | G-L7-10/1/D | — | G-L7-10/1/D |
| 16 | G-L7-16/1/D | — | G-L7-16/1/D |
| 20 | G-L7-20/1/D | — | G-L7-20/1/D |
| 25 | G-L7-25/1/D | — | G-L7-25/1/D |
| 32 | G-L7-32/1/D | — | G-L7-32/1/D |
| 40 | G-L7-40/1/D | — | G-L7-40/1/D |
Open original at full size ↗ Catalog page 04 · 3P, 3P+N and 4P ordering matrix with circuit diagrams
C curve | In (A) | 3P | 3P+N | 4P |
| 0.5 | G-L7-0.5/3/C | — | — |
| 1 | G-L7-1/3/C | — | G-L7-1/4/C |
| 2 | G-L7-2/3/C | — | — |
| 3 | G-L7-3/3/C | — | G-L7-3/4/C |
| 4 | G-L7-4/3/C | — | — |
| 6 | G-L7-6/3/C | G-L7-6/1N-2/C | G-L7-6/4/C |
| 10 | G-L7-10/3/C | G-L7-10/3N-2/C | G-L7-10/4/C |
| 16 | G-L7-16/3/C | G-L7-16/3N-2/C | G-L7-16/4/C |
| 20 | G-L7-20/3/C | G-L7-20/3N-2/C | G-L7-20/4/C |
| 25 | G-L7-25/3/C | G-L7-25/3N-2/C | G-L7-25/4/C |
| 32 | G-L7-32/3/C | G-L7-32/3N-2/C | G-L7-32/4/C |
| 40 | G-L7-40/3/C | G-L7-40/3N-2/C | G-L7-40/4/C |
| 50 | G-L7-50/3/C | G-L7-50/3N-2/C | G-L7-50/4/C |
| 63 | G-L7-63/3/C | G-L7-63/3N-2/C | G-L7-63/4/C |
D curve | In (A) | 3P | 3P+N | 4P |
| 2 | G-L7-2/3/D | G-L7-2/3N/D | — |
| 4 | G-L7-4/3/D | G-L7-4/3N/D | — |
| 6 | G-L7-6/3/D | G-L7-6/3N/D | — |
| 10 | G-L7-10/3/D | G-L7-10/3N/D | — |
| 16 | G-L7-16/3/D | G-L7-16/3N/D | — |
| 20 | G-L7-20/3/D | G-L7-20/3N/D | — |
| 25 | G-L7-25/3/D | G-L7-25/3N/D | — |
| 32 | G-L7-32/3/D | G-L7-32/3N/D | — |
| 40 | G-L7-40/3/D | G-L7-40/3N/D | — |
Open original at full size ↗ Back to series selection ↑
G-L7-DC Miniature Circuit Breakers
L7-GL-FUSE CATALOG · PRINTED PAGES 01, 06
The DC chapter covers G-L7Z C-curve DC breakers in one- through four-pole configurations. The page 01 overview also shows a separate G-L7-DC40 product; select the matching model and wiring diagram.
G-L7Z DC pole configurations
G-L7-DC40 catalog overview
DC catalog specifications · pp. 01, 06 | Parameter | Catalog value |
| G-L7Z rated-current order rows | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50 and 63 A |
| Pole options in ordering table | 1P, 2P, 3P and 4P |
| Breaking capacity and curve shown | 6 kA; C curve; instantaneous trip 5–10 × In |
| Connection examples | 250 V DC with one pole; 500 V DC with two poles as wired in the diagram; T = 4 ms |
| G-L7-DC40 overview (p. 01) | 500/1000 V; 6, 10, 16, 20, 25, 32 and 40 A |
Catalog verification. The 500/1000 V entry is for the separate DC40 overview. Use the configuration-specific diagrams on page 06 for G-L7Z polarity and series pole connection.
Catalog page 06 · DC product, circuit symbols and order codes
G-L7Z C-curve order codes | In (A) | 1P | 2P | 3P | 4P |
| 1 | G-L7Z-1/1/C-DC | G-L7Z-1/2/C-DC | G-L7Z-1/3/C-DC | G-L7Z-1/4/C-DC |
| 2 | G-L7Z-2/1/C-DC | G-L7Z-2/2/C-DC | G-L7Z-2/3/C-DC | G-L7Z-2/4/C-DC |
| 3 | G-L7Z-3/1/C-DC | G-L7Z-3/2/C-DC | G-L7Z-3/3/C-DC | G-L7Z-3/4/C-DC |
| 4 | G-L7Z-4/1/C-DC | G-L7Z-4/2/C-DC | G-L7Z-4/3/C-DC | G-L7Z-4/4/C-DC |
| 6 | G-L7Z-6/1/C-DC | G-L7Z-6/2/C-DC | G-L7Z-6/3/C-DC | G-L7Z-6/4/C-DC |
| 10 | G-L7Z-10/1/C-DC | G-L7Z-10/2/C-DC | G-L7Z-10/3/C-DC | G-L7Z-10/4/C-DC |
| 16 | G-L7Z-16/1/C-DC | G-L7Z-16/2/C-DC | G-L7Z-16/3/C-DC | G-L7Z-16/4/C-DC |
| 20 | G-L7Z-20/1/C-DC | G-L7Z-20/2/C-DC | G-L7Z-20/3/C-DC | G-L7Z-20/4/C-DC |
| 25 | G-L7Z-25/1/C-DC | G-L7Z-25/2/C-DC | G-L7Z-25/3/C-DC | G-L7Z-25/4/C-DC |
| 32 | G-L7Z-32/1/C-DC | G-L7Z-32/2/C-DC | G-L7Z-32/3/C-DC | G-L7Z-32/4/C-DC |
| 40 | G-L7Z-40/1/C-DC | G-L7Z-40/2/C-DC | G-L7Z-40/3/C-DC | G-L7Z-40/4/C-DC |
| 50 | G-L7Z-50/1/C-DC | G-L7Z-50/2/C-DC | G-L7Z-50/3/C-DC | G-L7Z-50/4/C-DC |
| 63 | G-L7Z-63/1/C-DC | G-L7Z-63/2/C-DC | G-L7Z-63/3/C-DC | G-L7Z-63/4/C-DC |
Open original at full size ↗ Back to series selection ↑
G-L71 1P+N Miniature Circuit Breakers
L7-GL-FUSE CATALOG · PRINTED PAGES 07–10
The G-L71 combines overload and short-circuit protection with neutral switching in one module. The catalog includes dimensions, C-curve order codes, temperature curves and separate D0 and NH fuse selectivity tables.
G-L71 1P+N miniature circuit breaker
Electrical specifications · p. 07 | Parameter | Catalog value |
| Rated voltage Ue | 230 V AC, 50/60 Hz |
| Rated current In | 6–40 A |
| Rated breaking capacity Icn | 6 kA |
| Trip characteristic in order table | C curve |
| Backup fuse shown | Maximum 100 A gL/gG for the condition marked >6 kA |
| Energy limitation class shown | 3 |
| Ambient temperature | −5 to +40 °C |
| Case protection | IP40 |
| Endurance | At least 8,000 switching operations |
Mechanical data · p. 07 | Parameter | Catalog value |
| Exposed face height | 45 mm |
| Enclosure height | 80 mm |
| Module width | 17.5 mm (1P+N) |
| Mounting | 35 mm DIN rail |
| Terminal capacity | 1–16 mm² |
Accessories listed · p. 07 | Parameter | Catalog value |
| Auxiliary contact | G-Z7-AHK |
| Alarm contact | G-Z7-NHK |
| Busbar | G-ZLV1V-10/… as printed |
Catalog verification. Page 10 includes general B, C and D trip-curve references. Page 08 lists C-curve G-L71 ordering codes.
Catalog page 08 · 1P+N product, wiring symbol and model table
C-curve 1P+N order codes | In (A) | 1P+N |
| 6 | G-L71-6/1N/C |
| 10 | G-L71-10/1N/C |
| 16 | G-L71-16/1N/C |
| 20 | G-L71-20/1N/C |
| 25 | G-L71-25/1N/C |
| 32 | G-L71-32/1N/C |
| 40 | G-L71-40/1N/C |
Open original at full size ↗ Catalog page 09 · D0 fuse selectivity table
D01, D02 and D03 · gL fuse rating (A) | Breaker In (A) | 16 | 20 | 25 | 35 | 50 | 63 | 80 | 100 |
| 6 | <0.5 | 0.6 | 0.9 | 2.3 | 5.0 | 6.0 | 6.0 | 6.0 |
| 10 | — | 0.5 | 0.7 | 1.5 | 3.0 | 4.5 | 6.0 | 6.0 |
| 13 | — | 0.5 | 0.7 | 1.3 | 2.7 | 4.0 | 6.0 | 6.0 |
| 20 | — | — | 0.6 | 1.1 | 2.2 | 3.0 | 5.5 | 6.0 |
| 16 | — | — | 0.6 | 1.1 | 2.1 | 2.9 | 5.2 | 6.0 |
| 25 | — | — | 0.5 | 1.0 | 2.0 | 2.7 | 4.8 | 6.0 |
| 32 | — | — | 0.5 | 1.0 | 1.9 | 2.6 | 4.5 | 6.0 |
| 40 | — | — | 0.5 | 0.9 | 1.7 | 2.3 | 4.0 | 6.0 |
Open original at full size ↗ Catalog page 10 · NH fuse selectivity table
NH-100 · gL fuse rating (A) | Breaker In (A) | 16 | 20 | 25 | 35 | 50 | 63 | 80 | 100 |
| 6 | <0.5 | 0.5 | 0.8 | 2.1 | 4.5 | 5.7 | 6.0 | 6.0 |
| 10 | — | — | 0.6 | 1.4 | 2.8 | 3.5 | 5.2 | 6.0 |
| 13 | — | — | 0.6 | 1.3 | 2.5 | 3.1 | 4.9 | 6.0 |
| 20 | — | — | 0.5 | 1.0 | 2.0 | 2.5 | 3.8 | 6.0 |
| 16 | — | — | 0.5 | 0.9 | 1.8 | 2.3 | 3.5 | 6.0 |
| 25 | — | — | 0.5 | 0.9 | 1.6 | 2.1 | 3.3 | 6.0 |
| 32 | — | — | — | 0.8 | 1.4 | 2.0 | 3.1 | 6.0 |
| 40 | — | — | — | 0.8 | 1.4 | 1.9 | 2.9 | 6.0 |
Open original at full size ↗ Back to series selection ↑