ATSL1 H Two Stage Power Transfer Isolation Switches
GWIEC DUAL POWER ATS CATALOG · PAGES 23–27
ATSL1/H is a two-stage transfer isolation switch series. The chapter documents N and NA model groups, and shows common-source priority transfer, controller options and wiring.
| Selection parameter | Catalog specification |
| Rated operational voltage in two-stage section | AC 400 V |
| Poles stated in two-stage section | 2P, 3P and 4P |
| N model tables | 16–63 A and 63–125 A groups |
| NA table models | ATSL1/H-32NA, -40NA, -63NA and -125NA |
| NA control functions listed | Generator-start signal, automatic/manual operation, adjustable 0–30 second delay, undervoltage and phase loss detection |
N type, page 24
| Parameter | ATSL1/H-16N | ATSL1/H-25N | ATSL1/H-32N |
| Rated current (A) | 16 | 25 | 32 |
| Operating current (A) | 3.5 | 3.5 | 3.5 |
| Short-time withstand (kA) | 3.5 | 3.5 | 3.5 |
| Poles | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P |
| Weight by poles (kg) | 3.2 / 3.7 / 4.2 | 4 / 4.5 / 5.5 | 4 / 4.5 / 5.5 |
| Mechanical / electrical life | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model |
| Operating cycle (s/operation) | 15 | 15 | 15 |
N type, page 24
| Parameter | ATSL1/H-40N | ATSL1/H-50N | ATSL1/H-63N |
| Rated current (A) | 40 | 50 | 63 |
| Operating current (A) | 3.5 | 3.5 | 3.5 |
| Short-time withstand (kA) | 3.5 | 3.5 | 3.5 |
| Poles | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P |
| Weight by poles (kg) | 4 / 4.5 / 5.5 | 4 / 4.5 / 5.5 | 4 / 4.5 / 5.5 |
| Mechanical / electrical life | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model |
| Operating cycle (s/operation) | 15 | 15 | 15 |
N type, page 25
| Parameter | ATSL1/H-63N | ATSL1/H-80N | ATSL1/H-100N | ATSL1/H-125N |
| Rated current (A) | 63 | 80 | 100 | 125 |
| Operating current (A) | 3.5 | 3.5 | 3.5 | 3.5 |
| Short-time withstand (kA) | 35 | 35 | 35 | 35 |
| Poles | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P |
| Weight by poles (kg) | 3.2 / 3.7 / 4.2 | 4 / 4.5 / 5.5 | 4 / 4.5 / 5.5 | 4 / 4.5 / 5.5 |
| Mechanical / electrical life | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model |
| Operating cycle (s/operation) | 15 | 15 | 15 | 15 |
NA type, page 26
| Parameter | ATSL1/H-32NA | ATSL1/H-40NA | ATSL1/H-63NA | ATSL1/H-125NA |
| Rated current (A) | 25, 32 | 40 | 63 | 125 |
| Operating current (A) | 3.5 | 3.5 | 3.5 | 3.5 |
| Short-time withstand (kA) | 5 | 5 | 5 | 5 |
| Poles | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P | 2P / 3P / 4P |
| Weight by poles (kg) | 4.2 / 4.7 / 5.2 | 5 / 5.5 / 6.5 | 5 / 5.5 / 6.5 | 5 / 5.5 / — |
| Mechanical / electrical life | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model | 8000 / 3000 for each model |
| Operating cycle (s/operation) | 15 | 15 | 15 | 15 |
Selection notes - The general description mentions 660 V and 32–6300 A. The detailed section lists AC 400 V and adds N models starting at 16 A. Verify the exact frame, voltage and controller.
- The 63N model appears in both N tables with different short-time withstand figures. The original tables are preserved separately. Confirm the applicable configuration.
- The NA table leaves the 125NA 4P weight blank.
Original diagrams and reference tables