| Availability: | |
|---|---|
| Quantity: | |
SC-3020 / SM-3025
GWIEC
Compare SC-3020 and SM-3025 by the catalog columns, complete electrical code and mechanical drawing. The first detection-distance cell is printed 2 mm ±10%; confirm this source inconsistency before selection.
| Outward appearance code | M40+M24 | M48+M24 | |
| Installation | Non-flush | Non-flush | |
| Detection distance | 2 mm ±10% (printed catalog value; confirm) | 25 mm ±10% | |
| Product photograph | View original image M40 + M24 product photograph | View original image M48 + M24 product photograph | |
| Output | NPN normally open | SC-3020A | SM-3025A |
| NPN normally closed | SC-3020B | SM-3025B | |
| NPN normally open + closed | SC-3020AB | SM-3025AB | |
| Output | PNP normally open | SC-3020C | SM-3025C |
| PNP normally closed | SC-3020D | SM-3025D | |
| PNP normally open + closed | SC-3020CD | SM-3025CD | |
| Output | DC two-wire normally open | SC-3020AL | SM-3025AL |
| DC two-wire normally closed | SC-3020BL | SM-3025BL | |
| Output | AC two-wire normally open | SC-2020A | SM-2025A |
| AC two-wire normally closed | SC-2020B | SM-2025B | |
| AC two-wire normally open + closed | SC-2020AB | SM-2025AB | |
| Technical parameters | |||
| Set distance | 0–0.7 mm (catalog; confirm) | 0–22 mm | |
| Standard target | Steel 65 x 65 x 1 mm | Steel 78 x 78 x 1 mm | |
| Supply voltage | 6–36 V DC; 90–250 V AC for AC variants | 6–36 V DC; 90–250 V AC for AC variants | |
| Switching point tolerance | ±10% | ±10% | |
| Load / output requirement | <200 mA | <200 mA | |
| Voltage drop | <2.5 V | <2.5 V | |
| Consumption current | <10 mA | <10 mA | |
| Hysteresis | 1–20% | 1–20% | |
| Repeatability | <3% | <3% | |
| Switching frequency | 500 Hz DC; 25 Hz AC for AC variants | 200 Hz DC; 25 Hz AC for AC variants | |
| Indicator | Red LED | Red LED | |
| Reverse polarity protection | Yes | Yes | |
| Surge protection | Yes | Yes | |
| Short circuit protection | Yes | Yes | |
| Ambient temperature | −25 to +70 °C | −25 to +70 °C | |
| Ambient humidity | 35–95% RH | 35–95% RH | |
| Protection rating | IP67 | IP67 | |
| Housing material | Nickel-plated brass | Nickel-plated brass | |
| Connection | 2 m PUR cable; M12 connector option shown | 2 m PUR cable; M12 connector option shown | |
| Catalog marking | CE symbol shown in catalog | CE symbol shown in catalog | |
| Engineering drawing Click to enlarge | View original image M40 + M24 / M48 + M24 engineering drawing | View original image M40 + M24 / M48 + M24 engineering drawing | |
Selection note: The SC-3020 set-distance cell reads 0–0.7 mm while the detection-distance cell is printed 2 mm. Confirm this operating-distance value before specification. AC and DC versions use different model codes.
Values are transcribed from the GWIEC sensor catalog, pages 11. A dash means no model is listed in that source cell. Nominal distance and an operating/set distance are different quantities. Select the complete model, output, supply, connection and mounting dimensions together.
Click any product photograph or engineering drawing to open the original image at full size.
Compare inductive sensor families · All proximity sensor categories · Contact GWIEC for model confirmation