VS1-12GD
GWIEC
Indoor three-station vacuum circuit breaker for 3.6–12 kV AC systems, integrating a vacuum circuit breaker, isolating switch, earthing switch, sensor and interlocking mechanism. The catalog specifies a 480 × 1000 × 1800 mm matching cabinet.
| Parameter | Unit | Catalog data |
|---|---|---|
| Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 |
| Rated current | A | 630; 1250 |
| 1 min power-frequency withstand voltage, interphase / across break | kV | 42 / 48 |
| Lightning impulse withstand voltage, interphase / across break | kV | 75 / 85 |
| Secondary circuit power-frequency withstand voltage, 1 min | V | 2000 |
| Rated short-circuit breaking current | kA | 20 / 25 / 31.5 |
| Rated peak withstand current | kA | 50 / 63 / 80 |
| Rated short-circuit making current | kA | 50 / 63 / 80 |
| 4 s rated short-time withstand current | kA | 20 / 25 / 31.5 |
| Rated short-time withstand duration | s | 4 |
| Rated breaking current of single / back-to-back capacitor bank | A | 630 / 400 |
| Rated capacitor-bank closing inrush current | kA | 12.5 (frequency ≤ 1000 Hz) |
| Rated short-circuit current breaking operations | operations | 30 |
| Mechanical life: isolating switch / circuit breaker / earthing switch | operations | 3000 / 10000 / 3000 |
| Cumulative permitted contact wear | mm | 3 |
| Rated closing and opening voltage | V | AC 24 / 48 / 110 / 220; DC 24 / 48 / 110 / 220 |
| Energy storage motor rated voltage | V | AC 24 / 48 / 110 / 220; DC 24 / 48 / 110 / 220 |
| Energy storage motor rated power | W | 70 |
| Energy storage time | s | ≤15 |
| Contact spacing | mm | 9±1 |
| Overtravel | mm | 3.5±1 |
| Contact closing bounce time | ms | ≤5 |
| Three-phase opening / closing phase difference | ms | ≤2 |
| Opening time at rated voltage | ms | ≤40 |
| Closing time at rated voltage | ms | ≤60 |
| Average opening speed | m/s | 0.9–1.3 |
| Average closing speed | m/s | 0.5–1.1 |
| Contact opening rebound amplitude | mm | ≤2 |
| Contact closing pressure | N | 2400±200 (20–25 kA); 3100+200 (31.5 kA, as printed) |
| Rated operating sequence | O–0.3s–CO–180s–CO |
Where the catalog presents several values in the same row, verify the applicable configuration before ordering. Source: catalog pages 27–28.
Dimensions in millimeters. The source catalog includes separate formal and anti-loading external dimensions; select the mounting configuration before ordering. The source drawings identify the isolating switch, fixed sealed pole, charged sensor and grounding switch.