ZN63A(VS1)-12(24)(C)
GWIEC
Side-mounted indoor vacuum circuit breaker for three-phase AC 50 Hz protection and control. The overview describes 12–24 kV series; the table below specifies the catalog’s 12 kV version. Confirm the exact configuration, breaking rating and installation dimensions before ordering.
| Parameter | Unit | 20 kA | 25 kA | 31.5 kA |
|---|---|---|---|---|
| Rated voltage | kV | 12 | 12 | 12 |
| Maximum working voltage | kV | 12 | 12 | 12 |
| Rated current | A | 630–1250 | 630–1600 | 630–1600 |
| Rated short-circuit breaking current | kA | 20 | 25 | 31.5 |
| Rated short-circuit making current | kA | 50 | 63 | 80 |
| Rated peak withstand current | kA | 50 | 63 | 80 |
| 4 s rated short-circuit withstand current | kA | 20 | 25 | 31.5 |
| 1 min power frequency withstand voltage | kV | 42 (across break 48) | 42 (across break 48) | 42 (across break 48) |
| Lightning impulse withstand voltage | kV | 75 (across break 84) | 75 (across break 84) | 75 (across break 84) |
| Operating sequence | O–0.3s–CO–180s–CO | O–0.3s–CO–180s–CO | O–0.3s–CO–180s–CO | |
| Mechanical life | operations | 10,000 | 10,000 | 10,000 |
| Short-circuit current breaking operations | operations | 50 | 50 | 50 |
| Closing and opening operating voltage | V | AC/DC 110, 220 | AC/DC 110, 220 | AC/DC 110, 220 |
| Contact opening distance | mm | 11±1 | 11±1 | 11±1 |
| Overtravel | mm | 3.5±0.5 | 3.5±0.5 | 3.5±0.5 |
| Three-phase closing/opening time difference | ms | ≤2 | ≤2 | ≤2 |
| Contact closing bounce time | ms | ≤2 | ≤2 | ≤2 |
| Average opening speed | m/s | 0.9–1.2 | 0.9–1.2 | 0.9–1.2 |
| Average closing speed | m/s | 0.5–0.8 | 0.5–0.8 | 0.5–0.8 |
| Tripping time at maximum voltage | s | ≤0.05 | ≤0.05 | ≤0.05 |
| Tripping time at minimum voltage | s | ≤0.08 | ≤0.08 | ≤0.08 |
| Closing time | s | 0.1 | 0.1 | 0.1 |
| Permitted contact wear thickness | mm | 3 | 3 | 3 |
The source lists phase resistance limits 630 A ≤50, 1250 A ≤45 and 1600 A ≤40 without a clear unit; verify before use.
Fixed mounting for suitable switchgear, ring main units and substations. Drawings and wiring information should be checked against the selected configuration. Source: printed catalog pages 24–26.