| Availability: | |
|---|---|
| Quantity: | |
ZN63A(VS1)-12(24)
GWIEC
Three-phase AC 50 Hz indoor vacuum circuit breaker designed for fixed or handcart mounting. The catalog describes 7.2–12 (24) kV variants; the main table below is for the 12 kV version. Confirm the exact installation type and rating when ordering.
| Parameter | Unit | Catalog value |
|---|---|---|
| Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 |
| 1 min power-frequency withstand voltage | kV | 42 |
| Rated lightning impulse withstand voltage | kV | 75 |
| Rated current | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 |
| Rated short-circuit breaking current / thermal withstand current | kA | 20, 25, 31.5, 40, 50; availability depends on rated current |
| Rated short-circuit making current / peak withstand current | kA | 50, 63, 80, 100, 125 |
| Thermal withstand duration | s | 4 |
| Mechanical life | operations | 30000 |
| Single capacitor-bank breaking current (when required) | A | 630 |
| Back-to-back capacitor-bank breaking current (when required) | A | 400 |
For 4000 A, the catalog calls for forced-air cooling. The catalog gives 30 and 50 short-circuit breaking operations and provides different operating sequences according to breaking-current rating; its limits overlap at 31.5 kA, so confirm the applicable version before selection.
| Rated current (A) | 630 | 1250 | 1600 | 2000 |
|---|---|---|---|---|
| Short-circuit breaking / thermal withstand current (kA) | 20 / 25 / 31.5 | 25 / 31.5 / 40 | 31.5 / 40 | 31.5 / 40 |
| Short-circuit making / peak withstand current (kA) | 50 / 63 / 80 | 63 / 80 / 100 | 80 / 100 | 80 / 100 |
| Rated current (A) | 2500 | 3150 | 4000 |
|---|---|---|---|
| Short-circuit breaking / thermal withstand current (kA) | 31.5 / 40 | 40 | 40 / 50 |
| Short-circuit making / peak withstand current (kA) | 80 / 100 | 100 | 100 / 125 |
| Rated current (A) | 630 | 1250 | 1600 |
|---|---|---|---|
| Rated breaking current (kA) | 20, 25, 31.5 | 25, 31.5, 40 | 31.5, 40 |
| Rated current (A) | 630 | 1250 | 1600 |
|---|---|---|---|
| Mating stationary contact diameter (mm) | 35 | 49 | 55 |
The catalog specifies contact engagement of 15–25 mm. Figures and ratings vary with phase spacing, 12 / 24 kV version, fixed or handcart mounting and pole structure; check each drawing and the selected configuration.
Each drawing is presented at full resolution; click to open its vector original.
| Version | Rated current (A) | Breaking current (kA) | Stationary contact diameter (mm) |
|---|---|---|---|
| 12 kV, 210 / 275 mm phase spacing | 630 | 20, 25, 31.5 | 35 |
| 12 kV, 210 / 275 mm | 1250 | 25, 31.5, 40 | 49 |
| 12 kV, 210 / 275 mm | 1600 | 31.5, 40 | 55 |
| 24 kV, 275 mm | 630 | 20, 25, 31.5 | 35 |
| 24 kV, 275 mm | 1250 | 25, 31.5 | 49 |
| 24 kV, 275 mm | 1600 | 31.5 | 55 |
| 24 kV, 275 mm | 2000 | 31.5, 40 | 79 |
| 24 kV, 275 mm | 2500–3150 | 31.5, 40 | 109 |
24 kV handcart travel: 300 mm; moving and stationary contact engagement: 15–25 mm. See drawings for individual configurations.
HQ: closing coil; TQ: opening coil; M: energy-storage motor; HK: auxiliary switch; Y1: optional closing locking coil; R1: resistor; S8/S9: handcart test/working position auxiliary switches; SP1–SP5: microswitches; X: 20-position plug-in terminal. K0: optional anti-jump relay; Y7–Y9: optional indirect overcurrent releases; L1–L11: jumpers; V1–V4: bridge rectifier.